Search
Close this search box.

Deluge valve

Deluge valve

Category
  • Certificate: UL Listed / FM Approved
  • Standard: UL 260
  • Connection: Flanged ANSI B16.1 Class 125, EN 1092 PN 16, grooved, etc.
  • Feature: Electrical actuation (Standard), vertical or horizontal installation
  • Temperature: 0°C to 87°C
  • W. pressure: 200 / 285 / 300 psi
  • Surface: FBE coating as AWWA C550

Product Details

Deluge valve is mainly used in high flow deluge system. It is a diaphragm valve to automatically control the system water flow, and it actuates upon the wet pilot line, dry pilot line, electrical signal, and emergency manual release.

Available size (Source 1 with UL)

Size Actuation type Connection Working pressure (psi) Ref. No.
2″ / DN50 Electrical / wet / dry FxF, GxG, FxG 300 V6701 (UL)
2-1/2″ / DN65 Electrical / wet / dry FxF, GxG, FxG 300 V6702 (UL)
3″ / DN80 Electrical / wet / dry FxF, GxG, FxG 300 V6703 (UL)
4″ / DN100 Electrical / wet / dry FxF, GxG, FxG 300 V6704 (UL)
6″ / DN150 Electrical / wet / dry FxF, GxG, FxG 300 V6705 (UL)
8″ / DN200 Electrical / wet / dry FxF, GxG, FxG 300 V6706 (UL)
10″ / DN250 Electrical / wet / dry FxF, GxG, FxG 300 V6707 (UL)
12″ / DN300 Electrical / wet / dry FxF, GxG, FxG 300 V6708 (UL)

Note:
1. For wet pilot line trim, it includes different trim pipeline.
2. For dry pilot line trim, it includes different trim pipeline, air compressor, pneumatic actuator.
3. The flanged end connection is available with ANSI B16.5 Class 150, ANSI B16.42 Class 150, BS 4504 PN 16, or DIN 2532 PN 16.

 

Available size (Source 2 with UL/FM)

Size Actuation type Connection Working pressure (psi) Ref. No.
3″ / DN80 Electrical / wet / dry FxF, GxG 300 V6711 (UL/FM)
4″ / DN100 Electrical / wet / dry FxF, GxG 300 V6712 (UL/FM)
6″ / DN150 Electrical / wet / dry FxF, GxG 300 V6713 (UL/FM)
8″ / DN200 Electrical / wet / dry FxF, GxG 300 V6714 (UL/FM)

Note:
1. For wet pilot line trim, it includes different trim pipeline.
2. For dry pilot line trim, it includes different trim pipeline, air compressor, pneumatic actuator.
3. The flanged end connection is available with BS 4504 PN 16, or DIN 2532 PN 16.

 

Available size (Source 3 with UL with more materials)

Size Actuation type Connection Working pressure (psi) Ref. No.
3″ / DN80 Electrical / wet / dry FxF, GxG 250 / 285 / 300 V6731 (UL)
4″ / DN100 Electrical / wet / dry FxF, GxG 250 / 285 / 300 V6732 (UL)
6″ / DN150 Electrical / wet / dry FxF, GxG 250 / 285 / 300 V6733 (UL)
8″ / DN200 Electrical / wet / dry FxF, GxG 250 / 285 / 300 V6734 (UL)
10″ / DN250 Electrical / wet / dry FxF 250 / 285 / 300 V6735 (UL)
12″ / DN300 Electrical / wet / dry FxF 250 / 285 / 300 V6736 (UL)

Note:
1. The material of the main valve body & cover is also available with cast steel ASTM A216-WCB, nickel aluminum bronze ASTM B148, SS, etc.
2. It is simple design with main valve, solenoid valve and auxiliary pilot valve, without pre-assembly components (Water motor gong, etc.)
3. The flanged end connection is available with ANSI B16.42 Class 150 / 300, ANSI B16.5 Class 150 / 300.

Ask For A Quick Quote

Email us at info@tpmcsteel.com or use the form below. Normally you will be replied within 2 hours during support hours.