Search
Close this search box.

Pressure switch (Pressure alarm switch)

Pressure switch (Pressure alarm switch)

Category
  • Certificate: UL Listed / FM Approved
  • Standard: UL 753 / FM 3132, comply to NFPA 13, 13D, 13R, 72
  • Connection: 1/2″ NPT male
  • Temperature: -40°C to 60°C
  • Operating pres.: 300 / 250 psi
  • Enclosure: IP66
  • Surface: Corrosion resistant finish

Product Details

Pressure switch is used in wet, dry, or other fire sprinkler system to detect an pressure increase or decrease from normal system pressure, so to transmit the signal automatically to local alarm system and fire pump control cabinet.

Available size

Application Switch Adjustment pressure range Factory set Ref. No.
Wet pipe system with alarm check valve, dry pipe, preaction, or deluge valve Single (One set of SPDT) / Double (Two sets of SPDT) 4 ~ 20 psi, or 4 ~ 15 psi 4 ~ 8 psi V8601
Dry pipe system, preaction, pressure tank, air and water supply Single (One set of SPDT) / Double (Two sets of SPDT) 10 ~ 100 psi, or 10 ~ 60 psi Operates on increase 50 psi and on decrease at 30 psi V8604
Wet pip system with excess pressure, pressure tank, air and water supply Single (One set of SPDT) / Double (Two sets of SPDT) 10 ~ 200 psi, or 25 ~ 225 psi Operates on increase 130 psi and on decrease at 110 psi V8612

Ask For A Quick Quote