Unshielded fire alarm cable (FPLR & FPL)

Unshielded fire alarm cable (FPLR & FPL)

  • Certificate: UL Listed
  • Standard: UL 1424 / NEC Article 760
  • Temperature: -20°C to 75°C
  • Voltage: 300 V
  • Compliance: FPLR/CMR/CL3R, flame test UL 1666
    FPL/CM/CMG/CL3, flame test UL 1685 or CSA FT4/IEEE 1202
  • Application: Riser fire alarm wiring, General purpose fire alarm wiring

Product Details

Unshielded fire alarm cable (FPLR & FPL) is a kind of cable without shielding.

Type FPLR power-limited fire alarm riser cable is suitable for use in a vertical run in a shaft or to penetrate one or more floors. The cable has fire-resistant characteristics capable of preventing fire travel from floor to floor.

Type FPL power-limited fire alarm cable is suitable for general purpose fire alarm use. The cable is fire resistant to the spread of fire. But it doesn’t include installation in riser, ducts and plenums unless the cable is installed in conduit.

Available size (Solid conductor)

Size Conductor type Conductor dia. (mm) Conductor sect. (mm2) Max DCR at 20°C, Ω/km Ref. No.
22 AWG x 4C Solid 0.64 x 4C 0.32 59.1 C0201
18 AWG x 2C Solid 1.02 x 2C 0.82 21.4 C0202
18 AWG x 4C Solid 1.02 x 4C 0.82 21.4 C0203
16 AWG x 2C Solid 1.29 x 2C 1.31 13.5 C0204
16 AWG x 4C Solid 1.29 x 4C 1.31 13.5 C0205
14 AWG x 2C Solid 1.63 x 2C 2.08 8.45 C0206
12 AWG x 2C Solid 2.05 x 2C 3.31 5.31 C0207

 

Available size (Stranded conductor)

Size Conductor type Conductor dia. (mm) Conductor sect. (mm2) Max DCR at 20°C, Ω/km Ref. No.
22 AWG x 4C 7 stranded 0.73 x 4C 0.32, min 55.4 C0211
18 AWG x 2C 7 stranded 1.16 x 2C 0.81, min 21.9 C0212
18 AWG x 4C 7 stranded 1.16 x 4C 0.81, min 21.9 C0213
16 AWG x 2C 7 stranded 1.46 x 2C 1.28, min 13.7 C0214
16 AWG x 4C 7 stranded 1.46 x 4C 1.28, min 13.7 C0215
14 AWG x 2C 7 stranded 1.85 x 2C 2.04, min 8.60 C0216
12 AWG x 2C 7 stranded 2.32 x 2C 3.26, min 5.41 C0217