Search
Close this search box.

Preaction valve

Preaction valve

Category
  • Certificate: UL Listed / FM Approved
  • Standard: UL 260, FM 1011/1012/1013
  • Connection: Flanged ANSI B16.1 Class 125, EN 1092 PN 16, grooved, etc.
  • Feature: Double interlocked (Standard), vertical or horizontal installation
  • Temperature: 0°C to 87°C
  • W. pressure: 300 psi
  • Surface: FBE coating as AWWA C550

Product Details

Preaction valve is mainly used in preaction system, which utilize compressed nitrogen or air in the system piping, and water under pressure is held below the deluge valve until electrical/pneumatic actuators operate.

Available size (Source 1 with UL)

Size Trim configuration Actuation Connection Working pressure (psi) Ref. No.
2″ / DN50 Double interlock P-P FxF, GxG, FxG 300 V6801 (UL)
2-1/2″ / DN65 Double interlock P-P FxF, GxG, FxG 300 V6802 (UL)
3″ / DN80 Double interlock P-P FxF, GxG, FxG 300 V6803 (UL)
4″ / DN100 Double interlock P-P FxF, GxG, FxG 300 V6804 (UL)
5″ / DN125 Double interlock P-P FxF, GxG, FxG 300 V6805 (UL)
6″ / DN150 Double interlock P-P FxF, GxG, FxG 300 V6806 (UL)
8″ / DN200 Double interlock P-P FxF, GxG, FxG 300 V6807 (UL)
10″ / DN250 Double interlock P-P FxF, GxG, FxG 300 V6808 (UL)
12″ / DN300 Double interlock P-P FxF, GxG, FxG 300 V6809 (UL)

Note:
1. For P-P actuation, it means pneumatic-pneumatic actuation.
2. The valve assembly must be worked with air pressure maintenance device and air compressor, and they are separately supplied.
3. The flanged end connection is available with ANSI B16.5 Class 150, ANSI B16.42 Class 150, BS 4504 PN 16, or DIN 2532 PN 16.

 

Available size (Source 2 with UL/FM)

Size Trim configuration Actuation Connection Working pressure (psi) Ref. No.
3″ / DN80 Double interlock E-P FxF, GxG 250 V6811 (UL/FM)
4″ / DN100 Double interlock E-P FxF, GxG 250 V6812 (UL/FM)
6″ / DN150 Double interlock E-P FxF, GxG 250 V6813 (UL/FM)
8″ / DN200 Double interlock E-P FxF, GxG 250 V6814 (UL/FM)
3″ / DN80 Single interlock Electrical / wet / dry FxF, GxG 250 V6815 (UL/FM)
4″ / DN100 Single interlock Electrical / wet / dry FxF, GxG 250 V6816 (UL/FM)
6″ / DN150 Single interlock Electrical / wet / dry FxF, GxG 250 V6817 (UL/FM)
8″ / DN200 Single interlock Electrical / wet / dry FxF, GxG 250 V6818 (UL/FM)

Note:
1. For E-P actuation, it means electrical-pneumatic actuation.
2. The valve assembly must be worked with air pressure maintenance device and air compressor, and they are separately supplied.
3. The flanged end connection is available with BS 4504 PN 16, or DIN 2532 PN 16.

Ask For A Quick Quote

Email us at info@tpmcsteel.com or use the form below. Normally you will be replied within 2 hours during support hours.