Vertical turbine fire pump from TPMC delivers robust, high-head water supply from deep wells, rivers, reservoirs, and sumps. Designed for applications where the water source is located below the pump, these multistage units feature a submerged bowl assembly driven by a long vertical shaft. Each additional stage increases discharge head, enabling customized pressure for tall buildings or extensive fire protection networks. The vertical design minimizes footprint while providing reliable flooded-suction operation without priming.
Available sizes (Electric motor drive)
| US system capacity (gpm) | US system pressure (psi) | Metric system capacity (m³/h) | Metric system pressure (bar) | Stages | Ref. No. |
|---|---|---|---|---|---|
| 500 | 43 ~ 277 | 114 | 3.0 ~ 19.1 | 3 ~ 9 | U0301 |
| 750 | 42 ~ 300 | 170 | 2.9 ~ 20.7 | 3 ~ 10 | U0302 |
| 1000 | 39 ~ 270 | 227 | 2.7 ~ 18.6 | 3 ~ 10 | U0303 |
| 1250 | 50 ~ 270 | 284 | 3.4 ~ 18.6 | 3 ~ 10 | U0304 |
| 1500 | 45 ~ 200 | 341 | 3.1 ~ 13.8 | 2 ~ 7 | U0305 |
| 2000 | 47 ~ 197 | 454 | 3.2 ~ 13.6 | 2 ~ 6 | U0306 |
| 2500 | 60 ~ 185 | 568 | 4.1 ~ 12.8 | 2 ~ 4 | U0307 |
| 3000 | 55 ~ 210 | 681 | 3.8 ~ 14.5 | 2 ~ 4 | U0308 |
| 3500 | 55 ~ 210 | 795 | 3.8 ~ 14.5 | 2 ~ 4 | U0309 |
| 4000 | 77 ~ 200 | 908 | 5.3 ~ 13.8 | 2 ~ 4 | U0310 |
| 4500 | 70 ~ 190 | 1022 | 4.8 ~ 13.1 | 2 ~ 4 | U0311 |
| 5000 | 70 ~ 180 | 1136 | 4.8 ~ 12.4 | 2 ~ 4 | U0312 |
Note:
1. The pressure ranges shown represent the available performance envelope across listed stage counts at nominal speeds. Actual performance curves and drive power selection are provided upon request for selected duty point. Contact TPMC for details.
2. All ratings comply with NFPA 20 (150% capacity at not less than 65% of rated head; shut-off head not more than 140% of rated head).
Available sizes (Diesel engine drive)
| US system capacity (gpm) | US system pressure (psi) | Metric system capacity (m³/h) | Metric system pressure (bar) | Stages | Ref. No. |
|---|---|---|---|---|---|
| 500 | 59 ~ 333 | 114 | 4.1 ~ 23.0 | 3 ~ 9 | U0321 |
| 750 | 82 ~ 368 | 170 | 5.7 ~ 25.4 | 3 ~ 10 | U0322 |
| 1000 | 65 ~ 272 | 227 | 4.5 ~ 18.8 | 3 ~ 10 | U0323 |
| 1250 | 65 ~ 290 | 284 | 4.5 ~ 20.0 | 3 ~ 10 | U0324 |
| 1500 | 70 ~ 247 | 341 | 4.8 ~ 17.0 | 2 ~ 7 | U0325 |
| 2000 | 64 ~ 281 | 454 | 4.4 ~ 19.4 | 2 ~ 6 | U0326 |
| 2500 | 67 ~ 280 | 568 | 4.6 ~ 19.3 | 2 ~ 4 | U0327 |
| 3000 | 55 ~ 220 | 681 | 3.8 ~ 15.2 | 2 ~ 4 | U0328 |
| 3500 | 70 ~ 220 | 795 | 4.8 ~ 15.2 | 2 ~ 4 | U0329 |
| 4000 | 78 ~ 200 | 908 | 5.4 ~ 13.8 | 2 ~ 4 | U0330 |
| 4500 | 70 ~ 190 | 1022 | 4.8 ~ 13.1 | 2 ~ 4 | U0331 |
| 5000 | 70 ~ 180 | 1136 | 4.8 ~ 12.4 | 2 ~ 4 | U0332 |
Note:
1. The pressure ranges shown represent the available performance envelope across listed stage counts at nominal speeds. Actual performance curves and drive power selection are provided upon request for selected duty point. Contact TPMC for details.
2. All ratings comply with NFPA 20 (150% capacity at not less than 65% of rated head; shut-off head not more than 140% of rated head).
Email us at info@tpmcsteel.com or use the form below. Normally you will be replied within 2 hours during support hours.