Single-stage end suction fire pump

Single-stage end suction fire pump

  • Certificate: UL Listed / FM Approved
  • Standard: NFPA 20
  • Configuration: Single-stage, end suction, top discharge
  • Flow: 150 ~ 1000 gpm (34 ~ 227 m³/h)
  • Pressure (Head): 40 ~ 151 psi (2.8 ~ 10.4 bar)
  • Speed: 2900 rpm (50 Hz) / 3500 rpm (60 Hz); 4-pole (1450/1750 rpm) available
  • Liquid: Clean water, 0°C ~ 40°C
  • Surface: Red FBE coating per AWWA C550

Product Details

Single-stage end suction fire pump from TPMC delivers dependable, high-head water supply for standpipe, sprinkler systems, and high-rise building fire protection. The compact volute casing and single impeller efficiently convert rotational energy into pressure. Back pull-out construction allows rapid access to internal components without disturbing piping or motor alignment, simplifying maintenance and reducing downtime.

Available sizes (Electric motor drive)

US system capacity (gpm) US system pressure (psi) Metric system capacity (m³/h) Metric system pressure (bar) Ref. No.
150 40 ~ 134 34 2.8 ~ 9.2 U0201
200 40 ~ 133 45 2.8 ~ 9.2 U0202
250 43 ~ 132 57 3.0 ~ 9.1 U0203
300 55 ~ 130 68 3.8 ~ 9.0 U0204
400 57 ~ 143 91 3.9 ~ 9.9 U0205
450 54 ~ 141 102 3.7 ~ 9.7 U0206
500 75 ~ 151 114 5.2 ~ 10.4 U0207
750 83 ~ 151 170 5.7 ~ 10.4 U0208
1000 80 ~ 145 227 5.5 ~ 10.0 U0209

Note:
1. The pressure ranges shown represent the available performance envelope at nominal speeds. Actual performance curves and drive power selection are provided upon request for selected duty point. Contact TPMC for details.
2. All ratings comply with NFPA 20 (150% capacity at not less than 65% of rated head; shut-off head not more than 140% of rated head).

Available sizes (Diesel engine drive)

US system capacity (gpm) US system pressure (psi) Metric system capacity (m³/h) Metric system pressure (bar) Ref. No.
150 40 ~ 139 34 2.8 ~ 9.6 U0221
200 40 ~ 138 45 2.8 ~ 9.5 U0222
250 41 ~ 136 57 2.8 ~ 9.4 U0223
300 48 ~ 134 68 3.3 ~ 9.2 U0224
400 42 ~ 146 91 2.9 ~ 10.1 U0225
450 54 ~ 146 102 3.7 ~ 10.1 U0226
500 65 ~ 150 114 4.5 ~ 10.3 U0227
750 63 ~ 151 170 4.3 ~ 10.4 U0228
1000 60 ~ 145 227 4.1 ~ 10.0 U0229

Note:
1. The pressure ranges shown represent the available performance envelope at nominal speeds. Actual performance curves and drive power selection are provided upon request for selected duty point. Contact TPMC for details.
2. All ratings comply with NFPA 20 (150% capacity at not less than 65% of rated head; shut-off head not more than 140% of rated head).

Ask For A Quick Quote