Single-stage end suction fire pump from TPMC delivers dependable, high-head water supply for standpipe, sprinkler systems, and high-rise building fire protection. The compact volute casing and single impeller efficiently convert rotational energy into pressure. Back pull-out construction allows rapid access to internal components without disturbing piping or motor alignment, simplifying maintenance and reducing downtime.
Available sizes (Electric motor drive)
| US system capacity (gpm) | US system pressure (psi) | Metric system capacity (m³/h) | Metric system pressure (bar) | Ref. No. |
|---|---|---|---|---|
| 150 | 40 ~ 134 | 34 | 2.8 ~ 9.2 | U0201 |
| 200 | 40 ~ 133 | 45 | 2.8 ~ 9.2 | U0202 |
| 250 | 43 ~ 132 | 57 | 3.0 ~ 9.1 | U0203 |
| 300 | 55 ~ 130 | 68 | 3.8 ~ 9.0 | U0204 |
| 400 | 57 ~ 143 | 91 | 3.9 ~ 9.9 | U0205 |
| 450 | 54 ~ 141 | 102 | 3.7 ~ 9.7 | U0206 |
| 500 | 75 ~ 151 | 114 | 5.2 ~ 10.4 | U0207 |
| 750 | 83 ~ 151 | 170 | 5.7 ~ 10.4 | U0208 |
| 1000 | 80 ~ 145 | 227 | 5.5 ~ 10.0 | U0209 |
Note:
1. The pressure ranges shown represent the available performance envelope at nominal speeds. Actual performance curves and drive power selection are provided upon request for selected duty point. Contact TPMC for details.
2. All ratings comply with NFPA 20 (150% capacity at not less than 65% of rated head; shut-off head not more than 140% of rated head).
Available sizes (Diesel engine drive)
| US system capacity (gpm) | US system pressure (psi) | Metric system capacity (m³/h) | Metric system pressure (bar) | Ref. No. |
|---|---|---|---|---|
| 150 | 40 ~ 139 | 34 | 2.8 ~ 9.6 | U0221 |
| 200 | 40 ~ 138 | 45 | 2.8 ~ 9.5 | U0222 |
| 250 | 41 ~ 136 | 57 | 2.8 ~ 9.4 | U0223 |
| 300 | 48 ~ 134 | 68 | 3.3 ~ 9.2 | U0224 |
| 400 | 42 ~ 146 | 91 | 2.9 ~ 10.1 | U0225 |
| 450 | 54 ~ 146 | 102 | 3.7 ~ 10.1 | U0226 |
| 500 | 65 ~ 150 | 114 | 4.5 ~ 10.3 | U0227 |
| 750 | 63 ~ 151 | 170 | 4.3 ~ 10.4 | U0228 |
| 1000 | 60 ~ 145 | 227 | 4.1 ~ 10.0 | U0229 |
Note:
1. The pressure ranges shown represent the available performance envelope at nominal speeds. Actual performance curves and drive power selection are provided upon request for selected duty point. Contact TPMC for details.
2. All ratings comply with NFPA 20 (150% capacity at not less than 65% of rated head; shut-off head not more than 140% of rated head).
Email us at info@tpmcsteel.com or use the form below. Normally you will be replied within 2 hours during support hours.