K14.0 ECOH (Extended coverage ordinary hazard) upright sprinkler is designed for use in ordinary hazard occupancies, and it provides max coverage area of 400 ft2 (37.2 m2) as NFPA 13.
Available size (Source 1 with UL)
Type | Temperature rating | Working pressure (psi) | Ref. No. |
---|---|---|---|
ECOH upright | 155°F (68°C) | 175 | S3601 (UL) |
ECOH upright | 175°F (79°C) | 175 | S3602 (UL) |
ECOH upright | 200°F (93°C) | 175 | S3603 (UL) |
ECOH upright | 286°F (141°C) | 175 | S3604 (UL) |
Note: As UL rule, it is SR sprinkler for OH (Ordinary hazard group I and II) at max coverage area (ft x ft) 16 x 16, 18 x 18, and 20 x 20, with different temperature rating. It is QR sprinkler for OH (Ordinary hazard group I and II) at max coverage area (ft x ft) 14 x 14, with different temperature rating.
Available size (Source 2 with UL)
Type | Temperature rating | Working pressure (psi) | Ref. No. |
---|---|---|---|
ECOH upright | 165°F (74°C) | 175 | S3621 (UL) |
ECOH upright | 212°F (100°C) | 175 | S3622 (UL) |
Note:
1. As UL rule, it is SR sprinkler for OH (Ordinary hazard group I and II) at max coverage area (ft x ft) 20 x 20.
2. The minum sprinkler spacing is 12 ft.