Clevis hanger from TPMC features a two-part assembly with a formed U-strap supporting the pipe from beneath and an upper yoke secured by a cross bolt. This robust design provides higher load capacity, greater rigidity, and easy vertical adjustment via the hanger rod connection, while reducing rod bending by allowing limited horizontal swing along the pipe axis.
UL Listed and FM Approved, this hanger is ideal for the suspension of insulated or non-insulated stationary horizontal piping in fire protection, HVAC, and industrial applications where higher load capacities are required.
Available sizes (Carbon steel material)
| Pipe size | Rod size (RS, imperial) | Rod size (RS, metric) | Max rec. load (lbs) | Ref. No. |
|---|---|---|---|---|
| 1/2″ / DN15 | 3/8″ | M10 | 610 | P4101 (UL) |
| 3/4″ / DN20 | 3/8″ | M10 | 610 | P4102 (UL/FM) |
| 1″ / DN25 | 3/8″ | M10 | 730 | P4103 (UL/FM) |
| 1-1/4″ / DN32 | 3/8″ | M10 | 730 | P4104 (UL/FM) |
| 1-1/2″ / DN40 | 3/8″ | M10 | 730 | P4105 (UL/FM) |
| 2″ / DN50 | 3/8″ | M10 | 730 | P4106 (UL/FM) |
| 2-1/2″ / DN65 | 1/2″ | M12 | 1350 | P4107 (UL/FM) |
| 3″ / DN80 | 1/2″ | M12 | 1350 | P4108 (UL/FM) |
| 4″ / DN100 | 5/8″ | M16 | 1430 | P4109 (UL/FM) |
| 5″ / DN125 | 5/8″ | M16 | 1430 | P4110 (UL/FM) |
| 6″ / DN150 | 3/4″ | M20 | 1940 | P4111 (UL/FM) |
| 8″ / DN200 | 3/4″ | M20 | 2000 | P4112 (UL/FM) |
| 10″ / DN250 | 3/4″ | M20 | 3600 | P4113 (UL/FM) |
| 12″ / DN300 | 3/4″ | M20 | 3800 | P4114 (UL/FM) |
| 14″ / DN350 | 1″ | M24 | 4200 | P4115 (ISO) |
Note: For more available sizes, please download the complete catalog (PDF).
Available sizes (Stainless steel material)
| Pipe size | Rod size (RS, imperial) | Rod size (RS, metric) | Max rec. load (lbs) | Ref. No. |
|---|---|---|---|---|
| 1/2″ / DN15 | 3/8″ | M10 | 600 | P4121 (ISO) |
| 3/4″ / DN20 | 3/8″ | M10 | 600 | P4122 (ISO) |
| 1″ / DN25 | 3/8″ | M10 | 600 | P4123 (ISO) |
| 1-1/4″ / DN32 | 3/8″ | M10 | 600 | P4124 (ISO) |
| 1-1/2″ / DN40 | 3/8″ | M10 | 600 | P4125 (ISO) |
| 2″ / DN50 | 3/8″ | M10 | 610 | P4126 (ISO) |
| 2-1/2″ / DN65 | 1/2″ | M12 | 1130 | P4127 (FM) |
| 3″ / DN80 | 1/2″ | M12 | 1130 | P4128 (FM) |
| 4″ / DN100 | 5/8″ | M16 | 1130 | P4129 (FM) |
| 5″ / DN125 | 5/8″ | M16 | 1430 | P4130 (FM) |
| 6″ / DN150 | 3/4″ | M20 | 1940 | P4131 (FM) |
| 8″ / DN200 | 3/4″ | M20 | 2000 | P4132 (FM) |
| 10″ / DN250 | 7/8″ | M22 | 3600 | P4133 (ISO) |
| 12″ / DN300 | 7/8″ | M22 | 3800 | P4134 (ISO) |
Note:
1. Load ratings are calculated with a minimum safety factor of 5:1 and apply at normal ambient temperatures. Values are based on the lesser of hanger rod tensile strength and clevis assembly capacity. For critical applications, consult project engineering specifications.
2. For insulated piping, use with appropriate pipe shields.
Email us at info@tpmcsteel.com or use the form below. Normally you will be replied within 2 hours during support hours.