Bib-nosed high pressure wet landing valve (PRV) from TPMC is designed with an integral pressure reducing valve to lower inlet pressure and maintain a constant reduced outlet pressure. This field-adjustable design protects downstream equipment, and ensures reliable firefighting supply in high-rise wet riser systems.
Available size (Source 1 with BSI/LPCB)
| Size | Inlet | Outlet | Working pressure (bar) | Ref. No. |
|---|---|---|---|---|
| DN 50 | Flanged DN 50, PN 25 | 2.5″ BS336 | 20 | FE1401 (BSI/LPCB) |
| DN 65 | Flanged DN 65, PN 25 | 2.5″ BS336 | 20 | FE1402 (BSI/LPCB) |
| DN 65 | 2.5″ BSPT, M | 2.5″ BS336 | 20 | FE1403 (BSI/LPCB) |
Note:
1. Inlet pressure range: 5.7 – 20 bar.
2. Outlet pressure regulation: 0 – 12 bar.
3. Outlet static pressure is factory‑preset at 7.0 bar (100 psi).
4. LPCB certified (Cert No. 1153Le) in TPMC models F29‑50, F29‑65, and F30‑65T.
Available size (Source 2 with FM)
| Size | Inlet | Outlet | Working pressure (bar) | Ref. No. |
|---|---|---|---|---|
| DN 80 | Flanged DN 80, PN 16 | 2.5″ BS336 / BSP / NH | 16 | FE1421 (FM) |
| DN 80 | Flanged 3″, Class 150 | 2.5″ BS336 / BSP / NH | 16 | FE1422 (FM) |
| DN 65 | 2.5″ BSPT, M | 2.5″ BS336 / BSP / NH | 16 | FE1423 (FM) |
Note:
1. Inlet pressure range: 4.8 – 20.7 bar.
2. Outlet pressure regulation: 3.5 – 9 bar.
3. Outlet static pressure is factory‑preset at 7.0 bar (100 psi).
Email us at info@tpmcsteel.com or use the form below. Normally you will be replied within 2 hours during support hours.